Spectrum-controls 1756sc-OF8H Series A Manuale Utente Pagina 74

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 170
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 73
60 ControlLogix
Analog HART Modules
Table 6.2c
Tag Name Data Type Style Description
Of8h0Input.ChanStatus SINT[8] BIN An array of 8 SINT which display
general status for each channel.
Of8h0Input.ChanStatus[X]
1
SINT BIN General channel status byte
Of8h0Input.ChanStatus[X].0
1
BOOL DEC User value exceeded high clamp
limit.
0 = No alarm
1 = Alarm
Of8h0Input.ChanStatus[X].1
1
BOOL DEC User value exceeded low clamp limit.
0 = No alarm
1 = Alarm
Of8h0Input.ChanStatus[X].2
1
BOOL DEC Specified ramp rate exceeded.
0 = No alarm
1 = Alarm
Of8h0Input.ChanStatus[X].3
1
BOOL DEC Channel holding last output value.
0 = Normal
1 = Holding
Of8h0Input.ChanStatus[X].4
1
BOOL DEC Channel calibration fault
0 = No fault
1 = Fault
Of8h0Input.ChanStatus[X].5
1,2
BOOL DEC Invalid or NaN channel value
0 = No alarm
1 = Alarm
Of8h0Input.ChanStatus[X].6
1
BOOL DEC Unused
Of8h0Input.ChanStatus[X].7
1
BOOL DEC Open wire fault (Current Only)
0 = No fault
1 = Fault
Of8h0Input.ChanData REAL[8] FLOAT An array of 8 floating point registers
which display the analog data for
each channel in engineering units.
Of8h0Input.ChanData[X]
1
REAL FLOAT Channel analog data in engineering
units
1
X represents the module channel number (0 to 7).
2
An invalid data value is being used for the associated channel's output tag (i.e. Of8h0.Output.ChXData)
Vedere la pagina 73
1 2 ... 69 70 71 72 73 74 75 76 77 78 79 ... 169 170

Commenti su questo manuale

Nessun commento